Enhance your motor drive system with the Marcus MLR0008N50 Open Line Reactor. Designed to reduce motor temperatures by 10°-20°C and minimize noise, this reactor limits inrush current to the drive rectifier, reducing peak current and harmonic distortion by up to 30%. It also minimizes voltage distortion, leading to a more efficient and quieter operation. Built with Marcus Transformers' expertise in designing products to withstand short circuits, this line reactor offers reliable protection for your equipment.The Marcus MLR0008N50 is an open-style line reactor with a voltage rating of 480V and an amperage rating of 8A. It features a 3% impedance and a 60 Hz frequency range. The inductance value is 5.00 mH, and it has a power rating of 3 hp. The operating temperature is rated at 155°C. Dimensions are 4.40 inches in length, 3.25 inches in height, and 3.50 inches in width, with mounting holes of 0.28 x 0.56 inches. It also has a loss rating of 30 Watts.