Enhance the performance and extend the life of your motors and drives with the Marcus MLR0012N25 Open-Type Line Reactor. This reactor is designed to minimize harmonic distortion, reduce inrush current, and limit peak current, leading to a typical current distortion reduction of up to 30%. It also helps to minimize voltage distortion, improving the overall waveform. By applying this line reactor, motor operating temperatures can be reduced by 10-20°C, and motor noise is significantly decreased due to the elimination of high-frequency harmonic currents. The reactor features a compact structure and is built with heat-proof insulation for durability and long life. It can withstand current under any short circuit conditions, thanks to Marcus Transformers Ltd.'s extensive experience in designing and testing components for demanding applications. This open-style line reactor is suitable for applications where strict limitations on harmonic distortion and noise level are required.The Marcus MLR0012N25 is an open-type, three-phase line reactor with a 3% impedance rating. It has a voltage rating of 600V and a current rating of 12A, with a corresponding horsepower rating of 10HP. The inductance is 2.5mH, and it operates at a fundamental frequency of 60Hz. The reactor is designed for compact size and long life, featuring heat-proof insulation and unique bobbin-wound coils for greater efficiency. It supports vertical or horizontal mounting and has terminal block connections.