ELECTRIC REGULATED POWER SUPPLY 100-240V AC, 5V 3.6 A, SINGLE PHASE, MODULAR

SC.ABLM1A05036
Stock : –
Availability of your Futech:
0
Total availability of Futech:
6
(some items may not be transferable)

996-ABLM1A05036 POWER SUPPLY 72082618 61NZ71 28AK5367 SCHABLM1A05036 3880946

Additional information :

This ABLM regulated switch mode power supply (SMPS) supplies direct current voltage. It has a rated input of 100V to 240V AC, a rated output current of 3,6A at 5V DC and a rated power output of 18W. It is ideal for supplying DC voltage necessary for automation equipment designed for applications in industrial, commercial and residential applications such as conveying, packaging, control, food & beverage, mining, oil & gas and water. It installs on omega rail or fixing by screw. Its width is 36mm, its height is 91mm, its depth is 55,6mm. It ensures a protection against overloads and short-circuits with automatic restart after the source of overload/short-circuit has been corrected. It weighs 0.170kg. It is a power supply for industrial use, rail mounting. It conforms to EN62368-1, ENIEC61010-1/2-201, ENIEC61204-3, EN61000-6-1/2/3/4, EN61000-3-2-3, UL62368-1, UL61010-2-201/-1-201, CSAC22.2No62368-1/No61010-2-201/No61010-1 standards, and certified by CE, CUL listed/recognized, RCM, CBscheme. The Acti9 iC60 range of Miniature Circuit Breakers is recommanded for its protection. The type of protection is 4A, B or C curve . It has in the front face a LED indicating presence of DC output voltage, and a QR code for access to the latest technical documentation. Thanks to their modular housing, they can be installed either in enclosures or industrial panels by clipping on omega (DIN) rail. It brings energy to your automated systems. Designed for simple machines and applications, modular power supplies are primarily appreciated for their extreme compactness. Specifications Main Range of product Modicon Power Supply Product or component type Power supply Power supply type Regulated switch mode Variant option Modular Enclosure material Plastic Nominal input voltage 100...240 V AC single phase 100...240 V AC 2 phases Rated power in W 18 W Output voltage 5 V DC Power supply output current 3.6 A Complementary Input voltage limits 90...264 V AC Nominal network frequency 50…60 Hz Network system compatibility TN TT IT Maximum leakage current 0.25 mA 240 V AC Input protection type Integrated fuse (not interchangeable) 3.15 A External protection (recommended) 20 A Curve B External protection (recommended) 20 A Curve C External protection (recommended) 4 A Curve B External protection (recommended) 4 A Curve C Inrush current 25 A at 115 V 50 A at 230 V Power factor 0.48 at 115 V AC 0.38 at 230 V AC Efficiency 80 % at 115 V AC 80 % at 230 V AC Output voltage adjustment 4.5...5.5 V Power dissipation in W 4.5 W Current consumption < 0.6 A 115 V AC < 0.4 A 230 V AC Turn-on time < 2 s Holding time > 20 ms 115 V AC > 60 ms 230 V AC Startup with capacitive loads 3000 µF Residual ripple < 100 mV Meantime between failure [MTBF] 2500000 h at 25 °C, full load 1000000 h at 55 °C, 80 % load Output protection type Against overload and short-circuits, protection technology: automatic reset Against over temperature, protection technology: manual reset Against overvoltage, protection technology: manual reset Connections - terminals Screw connection: 0.5...1.5 mm², (AWG 20...AWG 16) without wire end ferrule for input/output Screw connection: 0.5...1 mm², (AWG 20...AWG 18) with wire end ferrule for input/output Line and load regulation < 0.5 % network in line < 1 % network 0 to 100 % load Status LED 1 LED (green) output voltage Depth 55.6 mm Height 91 mm Width 36 mm Net weight 0.170 kg Output coupling Serial Mounting support Top hat type TH35-15 rail conforming to IEC 60715 Top hat type TH35-7.5 rail conforming to IEC 60715 Double-profile DIN rail Panel mounting Supply SELV conforming to EN/IEC 60950-1 SELV conforming to EN/IEC 60204-1 SELV conforming to IEC 60364-4-41 Dielectric strength 3000 V AC input/output Environment Standards EN 62368-1 EN/IEC 61010-1 EN 61010-2-201 EN/IEC 61204-3 EN 61000-6-1 EN 61000-6-2 EN 61000-6-3 EN 61000-6-4 EN 61000-3-2 EN 61000-3-3 UL 62368-1 UL 61010-1 UL 61010-2-201 CSA C22.2 No 62368-1 CSA C22.2 No 61010-1 CSA C22.2 No 61010-2-201 EN/IEC 62368-1 Product certifications CE CUL listed CUL recognized RCM CB Scheme EAC KC NEC: class 2 Operating altitude < 2000 m overvoltage category III 2000 m...5000 m overvoltage category II Shock resistance 100 m/s² for 11 ms IP degree of protection IP20 Ambient air temperature for operation -25…55 °C without current derating mounting position A < 2000 m 55…70 °C with current derating of 2.67 % per °C mounting position A < 2000 m Electrical shock protection class Class II without PE connection Pollution degree 2 Vibration resistance 3 mm (f= 2…9 Hz) conforming to IEC 60721-3-3 10 m/s² (f= 9…200 Hz) conforming to IEC 60721-3-3 Electromagnetic immunity Immunity to electrostatic discharge - test level: 6 kV (contact discharge) conforming to EN/IEC 61000-4-2 Immunity to electrostatic discharge - test level: 9 kV (air discharge) conforming to EN/IEC 61000-4-2 Electromagnetic field immunity test - test level: 10 V/m (80 MHz...2 GHz) conforming to EN/IEC 61000-4-3 Electromagnetic field immunity test - test level: 5 V/m (2...2.7 GHz) conforming to EN/IEC 61000-4-3 Electromagnetic field immunity test - test level: 3 V/m (2.7...6 GHz) conforming to EN/IEC 61000-4-3 Immunity to fast transients - test level: 4 kV (on input-output) conforming to EN/IEC 61000-4-4 Surge immunity test - test level: 3 kV (between power supply and earth) conforming to EN/IEC 61000-4-5 Surge immunity test - test level: 1.5 kV (between phases) conforming to EN/IEC 61000-4-5 Immunity to conducted disturbances - test level: 10 Vrms (0.15...80 MHz) conforming to EN/IEC 61000-4-6 Immunity to magnetic fields - test level: 30 A/m (50...60 Hz) conforming to EN/IEC 61000-4-8 Immunity to voltage dips - test level: 100 % (1 cycle) conforming to EN/IEC 61000-4-11 Immunity to voltage dips - test level: 60 % (10 cycles) conforming to EN/IEC 61000-4-11 Immunity to voltage dips - test level: 30 % (25 cycles) conforming to EN/IEC 61000-4-11 Disturbing field emission conforming to EN 55016-2-3 Limits for harmonic current emissions conforming to EN 61000-3-2 Conducted disturbance emission conforming to EN 55016-1-2 Conducted disturbance emission conforming to EN 55016-2-1 Electromagnetic emission Conducted emissions conforming to EN 61000-6-3 Radiated emissions conforming to EN 61000-6-4

Manufacturer: SCHNEIDER ELECTRIC