STANDARD CONTROL UNIT, TESYS ULTRA, 0.35A TO 1.4A, 3P MOTORS, THERMAL MAGNETIC PROTECTION, CLASS 10, COIL 24VDC

SC.LUCA1XBL
Availability of your Futech:
0
Total availability of Futech:
7
(some items may not be transferable)

Additional information :

TeSys U standard control unit to be inserted in power bases LUB12, LUB32, LUB38 to form a TeSys U starter controller, for 3-phase motor applications up to 0.25kW@400V. It provides full protection to motors with a rated current Ir 0.35-1.4A (Ir adjustable), overload tripping class 10, short circuit at 13 x Irmax, overcurrent at 14.2 x Ir, phase loss, insulation fault (protection of equipment only). To be used with a 24V DC voltage for the control of the starter (through the control terminals A1/A2 located in the power base). Certified when used in conjunction with a LUB power base (IEC, UL, CSA, CCC, EAC, Marine).

Amperage: 300mA-1.4A
Manufacturer: Schneider Electric