Specifications Main Range of product Modicon MCM Device short name XPSMCM Electrical connection Screw terminal Product or component type Safety controller CPU [Us] rated supply voltage 24 V - 20...20 % DC Number of inputs 8 digital for input connection 4 digital for interlock start/restart or external device monitoring Number of outputs 4 safety outputs OSSD for contactor/drive connection 4 test for line control outputs 4 configurable for diagnostic connection Discrete input voltage 24 V Discrete output current 400 mA Discrete input current 400 mA Discrete input type Safety input NPN or PNP Discrete output type PNP or NPN Function of module Emergency stop conforming to ISO 13850 Guard monitoring conforming to EN/ISO 14119 Enabling switch monitoring conforming to IEC 60947-5-1 Light curtain monitoring conforming to IEC 61496-1 Foot switch monitoring conforming to IEC 60947-5-1 Light curtain monitoring conforming to EN/ISO 14119 Switch monitoring conforming to EN 574 Two-hand control conforming to EN/ISO 14119 Safety mat monitoring conforming to IEC 61326-1 Switch monitoring conforming to IEC 61800-5-2 Muting function of light curtains conforming to IEC 61800-5-2 Safety time delays Counter functions Backplane connector Without Complementary Synchronisation time between inputs < 0.5 ms Power dissipation in W 3 W Maximum number of I/O expansion module 14 with 128 discrete output(s) for input 14 with 32.0 discrete output(s) for output Integrated connection type Backplane expansion bus USB 2.0 port Data storage equipment SD card (optional) Inductive load 2 mH Load capacitance 0.82 µF Safety level Can reach category 4 conforming to ISO 13849-1 Can reach PL = e conforming to ISO 13849-1 Type 4 conforming to IEC 61496-1 SILCL 3 conforming to IEC 62061 Can reach SILCL 1 conforming to ISO 13849-1 Quality labels CE Local signalling 1 LED green with PWR marking for power ON 1 LED green with RUN marking for RUN (status) 1 LED red with E IN marking for internal error 1 LED red with E EX marking for external error 1 LED orange with COM marking for communication 1 LED blue with EN marking for master enable 8 LEDs yellow with IN marking for input status 2 LEDs yellow with RST marking for restart signal 2 LEDs yellow with STATUS marking for output channel 1 LED green/red with MS marking for module status 1 LED green/red with NS marking for network status Connections - terminals 6 captive screw terminals, removable terminal block Cable cross section 0.2…1.5 mm² - AWG 24...AWG 16 flexible cablewithout cable end 0.2…2.5 mm² - AWG 24...AWG 14 flexible cablewithout cable end 0.25…1 mm² - AWG 23...AWG 18 flexible cablewith cable end, without bezel 0.25…2.5 mm² - AWG 23...AWG 14 flexible cablewith cable end, with bezel 0.25…1.5 mm² - AWG 23...AWG 16 flexible cablewith cable end, without bezel 0.5…1.5 mm² - AWG 20...AWG 16 flexible cablewith cable end, with double bezel 0.2…1 mm² - AWG 24...AWG 18 solid cablewithout cable end 0.2…2.5 mm² - AWG 24...AWG 14 solid cablewithout cable end Mounting support Omega 35 mm DIN rail conforming to EN 50022 Depth 114.5 mm Height 99 mm Width 45 mm Product weight 0.225 kg Environment Standards IEC 61496-1 ISO 13849-1 IEC 61508 IEC 61800-5-1 IEC 62061 Product certifications TÜV RCM cULus IP degree of protection IP20 Ambient air temperature for operation -10…55 °C Ambient air temperature for storage -20…85 °C Relative humidity 10…95 % Pollution degree 2 [Uimp] rated impulse withstand voltage 4 kV conforming to IEC 61800-5-1 Safety reliability data high DC > 99 % Insulation 250 V AC between power supply and housing conforming to IEC 61800-5-1 Overvoltage category II Electromagnetic compatibility Electrostatic discharge immunity test - test level: 6 kV (on contact) conforming to IEC 61000-4-2 Electrostatic discharge immunity test - test level: 20 kV (on air) conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields - test level: 10 V/m (80...1000 MHz) conforming to IEC 61000-4-3 Susceptibility to electromagnetic fields - test level: 30 V/m (1.4 GHz...2 GHz) conforming to IEC 61000-4-3 Vibration resistance +/-0.35 mm (f= 10…55 Hz) conforming to IEC 61496-1 Shock resistance 10 gn (duration = 16 ms) for 1000 shocks on each axis conforming to IEC 61496-1 service life 20 year(s)