Switching Digital Input Modules P or N; reverse protection
polarity up to 3 wires +FE.
Features:
Dimensions and weight
Depth 76mm (2.992 inch)
Height 120mm (4.724 inch)
Width 11.5mm (0.453 inch)
Fixing dimension height 128 mm
Net weight 87g
Temperatures:
Storage temperature -40°C ... +85°C
Operating temperature -20°C ... +60°C
Operating temperature, min. -20°C
Operating temperature, max. 60°C
Ratings:
ETIM 6.0 EC001599 ETIM 7.0 EC001599
ETIM 8.0 EC001599 ECLASS 9.0 27-24-26-04
ECLASS 9.1 27-24-26-04 ECLASS 10.0 27-24-26-04
ECLASS 11.0 27-24-26-04 ECLASS 12.0 27-24-26-04
Power supply::
Current consumption per INPUT (the corresponding supply segment) < 10 mA + sensor supply
Reverse polarity protection Yes
Current consumption per Isystemtyp. 8mA
Supply voltage 24 V DC +20 %/ -15 %, via bus system
Connection characteristics:
Conductor connection cross-section, max. 1.5mm²
Conductor connection cross-section, min. 0.14mm²
Conductor cross-section, rigid, max. (AWG) AWG 16
Conductor connection cross-section, rigid, min. (AWG) AWG 26
Conductor connection cross-section, flexible, max. 1.5mm²
Conductor connection cross-section, flexible, min. 0.14mm²
Conductor cross-section, flexible, max. (AWG) AWG 16
Conductor cross-section, flexible, min. (AWG) AWG 26
Connection type PUSH IN
Main Features:
Overvoltage category II
Shock 15 g over 11 ms, half sine wave, according to IEC 60068-2-27
Flammability class according to UL 94 V-0
Pollution Degree 2
Air humidity (operation) 10% to 95%, non-condensing, according to DIN EN 61131-2
Air humidity (storage) 10% to 95%, non-condensing, according to DIN
EN 61131-2
Air humidity (transport) 10% to 95%, non-condensing, according to DIN EN 61131-2
Air pressure (operation) = 795 hPa (height = 2000 m) according to DIN EN 61131-2
Air pressure (storage) 1013 hPa (height 0 m) to 700 hPa (height 3000 m) according to DIN EN 61131-2
Air pressure (transport) 1013 hPa (height 0 m) to 700 hPa (height 3000 m) according to DIN EN 61131-2
Rail TS 35
Test voltage 500V
Vibration resistance 5 Hz = f = 8.4 Hz: amplitude 3.5 mm according to IEC 60068-2-6, 8.4 Hz = f = 150 Hz: acceleration 1 g according to IEC 60068-2-6