The innovative user-centric IP20-confrom remote I/O concept:
Individual planning, fast installation, safe commissioning, preventing downtime. Significatly improved performance, higher productivity levels.
U-remote's small-size products with their lower number of feeder terminals help you minimise the space taken up by switchboard cabinets.
Tool-free installtion, modular assembly and a built-in web server speed up fitting the products to enclosures and machinery.
Status LEDs right at the conduit and on all u-remote modules enable quick troubleshooting and fast MRO.
Technical data:
No. of digital inputs (max.) 4
No. of inputs (max.) 4
Operating voltage 24 V DC (max)
Max. operating voltage 24 V DC
Operating voltage 24 V DC
Input voltage High:> 11 V
Input voltage Low:< 5 V
Height 120 mm
Length 76 mm
Width 11.5 mm
IP rating IP20
Dim (L x W x H) 76 x 11.5 x 120 mm
Type UR20-4COM-IO-LINK
Max. ambient temperature +60 °C
Min. ambient temperature -20 °C
Operating temperature, max.: 60 °C
Operating temperature, min.: -20 °C
Storage temperature: -40 °C ... +85 °C
Weight 87.62 g
Mounting dimensions Height: 128 mm
Product type PLC input module
Flammability class according to UL 94: V-0
Test voltage: 500 V
Shock: 15 g over 11 ms, half sine wave, according to IEC 60068-2-27
Pollution degree: 2
Vibration resistance: 5 Hz = f = 8.4 Hz: 3.5 mm amplitude acc. To IEC 60068-2-6, 8.4 Hz = f = 150 Hz: 1 g acceleration according to IEC 60068-2-6
Overvoltage category: II
Connection type: Push IN
Module type: Function module
Interface: U-remote system bus
Transmission rate System bus, max.: 48 Mbit
Conductor cross-section, single-wire, max.: 1.5 mm²
Conductor cross-section, single-wire, min.: 0.14 mm²
Conductor cross-section, single-wire, max. (AWG): AWG 16
Conductor cross-section, single-wire, min. (AWG): AWG 26
Conductor cross-section, fine-wired, max. (AWG): AWG 16
Conductor cross-section, fine-wired, min. (AWG): AWG 26
Conductor cross-section, fine-wired, min.: 0.14 mm²
Conductor cross-section, fine-wired, max.: 1.5 mm²
Single-channel diagnostics: Yes
Module diagnostics: Yes
Fieldbus protocol: CANopen, DeviceNet, EtherCAT, Ethernet/IP, Modbus/TCP, PROFINET IRT, PROFIBUS DP-V1, POWERLINK
Galvanic separation: DC 500 V between current paths
Current consumption from IIN (power segment of the fieldbus coupler), type: 8 mA