Inputs can be parameterised; up to 3-wire + FE; accuracy 0.1% FSR.
Variants are available with 12- and 16-bit resolution, which record up to 4 analogue sensors with +/-10 V, +/-5 V, 0...10 V, 0...5 V, 2...10 V, 1...5 V, 0...20 mA or 4...20 mA with maximum accuracy.
Each plug-in connector can optionally connect sensors with 2- or 3-
wire technology.
The parameters for the measurement range can be individually set for each channel.
In addition, each channel has its own status LED.
Technical data:
Dimensions and weights:
Depth 76 mm (2.992 inch)
Height 120 mm ( 4.724 inch)
Width 11.5 mm ( 0.453 inch)
Mounting dimension - height 128 mm
Net weight 88 g
Temperatures:
Storage temperature -40 °C ... +85 °C
Operating temperature -20 °C ... +60 °C
Environmental Product Compliance:
REACH SVHC Lead 7439-92-1
SCIP 82327f13-cd27-455aab5b-a62e1996dcf8
Analogue Inputs:
Accuracy 0.1% FSR
Conversion time 1 ms
Internal resistance I 250
Module diagnosis Yes
Number of analogue inputs 4
Reverse polarity protection Yes
Sensor supply Yes
Resolution 16 Bit
Sensor connection 2-wire, 3-wire, 4-wire
Individual channel diagnosis Yes
Input value Current I (0…20 mA, 4…20 mA)
Connection data:
Type of connection PUSH IN
Wire connection cross section, finely stranded, min. 0.14 mm²
Wire connection cross section, finely stranded, max. 1.5 mm²
Wire cross-section, finely stranded, max. (AWG) AWG 16
Wire cross-section, finely stranded, min. (AWG) AWG 26
Wire cross-section, solid, max. (AWG) AWG 16
Wire cross-section, solid, min. (AWG) AWG 26
Wire cross-section, solid, max. 1.5 mm²
Wire cross-section, solid, min. 0.14 mm²