Input Single Phase Nominal Input Voltage Ue Nom 1 x 100 … 240 V AC Input Voltage Range 1 x 90 … 264 V AC; 125 … 375 V DC Nominal Mains Frequency Range 47 … 63 Hz; 0 Hz Input Current Ie = 1 A (230 V AC); = 2 A (115 V AC) Starting Current = 18 A Power Factor Correction (PFC) Passive Mains Failure Delay = 10 ms (230 V AC) Output Nominal Output Voltage Us nom. 24 V DC (SELV) Output Voltage Range 22 … 26 V DC (adjustable) DC Preset 24 V Nominal Output Current Is Nom 5 A (24 V DC; 110 … 240 V AC); 4 A (24 V DC; 100 … 240 V AC) Nominal Output Power 120 W Adjustment Accuracy = 1% Residual Ripple = 200 mV (Peak - Peak) Overload Behavior Constant power (within the overload range 1.05 … 1.4 x Ia nom.); in case of short circuit or sustained overload, automatic power-off and power-up Signaling and Communication Signaling 1 x LED DC O.K. (green) Operating Status Indication Green LED (Ua) Efficiency/Power Dissipation Power Dissipation Pv = 19 W Typical Efficiency 88% (230 V AC; 5 A DC) Fuse Protection Internal Fuse F 2.5 A / 250 V AC Upstream Fuse (Required) For DC input voltage, an external DC fuse is required. For DC input voltage, an external DC fuse is required. Upstream Fuse (Recommended) Circuit Breaker B6, B10